14.01.2019
139/185
SYSTEM POS: XXXXX
Comp/cond OFF XXX External return digital input Rücklauf
Load shed 1 XXX
Load shedding 1 digital input
Load shed
2 XXX
Load shedding 2 digital input
Load shed
3 XXX
Load shedding 3 digital input
Cons.enab.CAN XXX Consumer enable via CAN bus
toggle Comp. XXX
Status digital output for FC compressor base load rotation for compressor combined control (only visible if
compressor combined control is activated: parameter Regelungsart on Combined Control menu 3-2-1-1-a)
Const.Press.V. XXX
Status of the digital output for the pressure maintenance valve
Bypass-valve XXX
Status of the digital output for the bypass valve
•
Menu 2-5 - Menu item is hidden
•
Menu 2-6 COP
COPPOS: XXXXX
COP Cool. X.XX
COP in cooling mode - updating only in cooling mode
COP HR X.XX
COP in heat recovery mode - always the current value
COP efficien. X.XX COP efficiency rating
•
Menu 2-7 Condenser monitoring
•
Menu 2-7a Condenser monitoring
10.1.4 Menu 3 Setpoints
SOLLWERTE POS: XXXXX
1 System configuration
Continue to menu 3-1
2 Regulation
Continue to menu 3-2
3 Verd.-Überwach.
Continue to menu 3-3
The condenser monitoring function must be deactivated (menu 3-9a set to "Off")!
The condenser monitoring function must be deactivated (menu 3-9a set to "Off")!