14.01.2019
154/185
HD-REG
POS: XXXXX
Input Def
ault
Di
m.
Neu SNr.:
"Manual Search": an ebmpapst fan can be added by entering its serial number (e.g.
1703000103).
10-
digit
numb
er
-
-
DEBUG
EBM
This screen is for the Modbus diagnostics of ebmpapst fans and is not described in detail.
Can only be set if authorisation = Master
•
Screen 3-2-2-1-a Type of control HP
REG.-ART POS: XXXXX
Input Default
Dim.
Step controller
√
Selection list of the HP control type
√
√
-
Drehzahlregler
-
Kombireg.parallel
-
Kombireg.stufen
-
•
Screen 3-2-2-1-b Switching order
LÜ.SCHRF POS:
XXXXX
Inp
ut
Defa
ult
Di
m.
xxxxxxxxxx
A:aa x
The switching order (of the stages in the gas cooler package) for the controller of the pack
controller is set in the submenu. The switching order must be assigned to the physical position
in the gas cooler package.
-- : Switching order has not been assigned and a message is output.
This state is not permissible; the fan must be disconnected from the power supply otherwise it
will run with 80% of its capacity in emergency operation.
0*: condenser fan is removed from the switching order list
* Can only be set if authorisation = Master
1..2
4
-
-
xxxxxxxxxx
A:aa x
Switching order of the second condenser fan
•
Screen 3-2-2-1-c EBM Manual ON
EBM-Lüft. POS: XXXXX
Input
Default
Dim.
xxxxxxxxxx A:aa x
...
Manual operation of ebmpapst fans. Each fan can be manually controlled between
0..100%.
-- : Manual mode deactivated - the fans are controlled via the controller
(automatic)
--, 0..100 ---
%
•
Screen 3-2-2-1-d Switch mode HP - star/delta operation
Schaltart POS: XXXXX
Input Default
Dim.
Direct
√
Loading and unloading of fan stages sequentially - default operating mode.
Star-delta operation is deactivated
√
√
-