14.01.2019
148/185
ND-REG T. POS:
XXXXX
Input Defa
ult
Dim
.
Vari.Z.LeiStu. OFF
→
Display of the variable times t
v
OFF
→
Screen
3-2-1-3-d
Neutrale Zone XX K Switching hysteresis for step control
1..10
4
K
NZ Drehz.reg. 0K
Neutral zone for the loading and unloading of fixed-speed compressors during
combined control
0..6
0
K
Regelkonstante XX
K
Max. control error for variable control times
1..15
10
K
Reg.m.Verd.AUS X
Deactivate high pressure controller when the last compressor is switched off Y/N
Y/N
N
-
•
Screen 3-2-1-3-a Basic time capacity stage ON
Basisz.EIN POS: XXXXX
Input Default
Dim.
Basisz.EIN S1 XXX s
Only the available capacity stages are displayed. 0..250 30
sec.
Basisz.EIN S2 XXX s
3..250
60
sec.
Basisz.EIN S3 XXX s
3..250
90
sec.
Basisz.EIN S4 XXX s
3..250
120
sec.
Basisz.EIN S5 XXX s
3..250
150
sec.
Basisz.EIN S6 XXX s
3..250
180
sec.
...
Basisz.EIN S12 XXX s
3..250
180
sec.
VS 3015 C base module: 1 - max. 4 capacity stages
with first SIOX extension module 1 - max. 8 capacity stages
with second SIOX extension module 1 - max. 12 capacity stages