14.01.2019
180/185
No
.
Message text
Message
18
8
•
Manual ON Sx
•
LT Manual ON Sx
•
ECO Manual ON Sx
•
Toggle to Manual ON - compressor stage Sx
•
LT compressor Sx Manual ON - LT compressor stage Sx
•
LT compressor Sx Manual ON - ECO compressor stage Sx
19
2
External fan
Currently not used
19
3
Emergency operation
Emergency operation / load shedding digital input 2 is active and emergency operation is
enabled
20
3
Sens. type change
A parameter for calibration of the pressure transmitters has been changed
20
4
Aut. lock Sx
Compressor stage x has been automatically locked (5x cylinder temperature too high per
day)
21
9
Meas. error MP
Error in the measuring circuit for measurement of the medium pressure
22
0
Messk. Gask.aust.
Fault in the measuring circuit for the gas cooler outlet temperature
22
1
High switching frequency
Switching frequency too high for compressor combined control
22
2
No load level
No load level information received for t0 shift via consumer
22
5
Meas. error suction gas
superheat.
Error in the measuring circuit for measurement of the suction gas superheat
23
1
Ext.to-shift
The signal for the external t0 shift (via CAN bus or analogue input 6, terminals 51/52) is faulty.
The to shift is not performed correctly.
23
2
M.err.ext.HP-shift
The signal for the external HP setpoint shift in HR mode (via analogue input 6, terminals
51/52) is faulty. The HP setpoint shift is not performed correctly.
23
3
High MP
Medium pressure too high
23
5
Meas. error HR outlet temp.
Fault in the measuring circuit for the HR outlet temperature
23
6
Meas. error suction gas
superheat.
Error in the measuring circuit for the suction gas superheat
23
7
Alarm HP-Valve
Fault in the high pressure valve
23
8
Alarm MP-Valve
Fault in the medium pressure valve
24
0
Setpoint change
A setpoint has been changed