14.01.2019
94/185
Function Colour LED
Description
Upper board (internal SIOX9
1 LIFE
green LED
Flashing: Active lamp, internal SIOX is supplied with power, processor is running
Off: Power supply interrupted or device defective
2 Error
red
LED
Flashing: Error indication (faulty communication between upper and lower board)
Off: No errors
3 Relay
outputs
green LED1
..
LED10
On: Relay is activated
ATTENTION DANGER TO LIFE: External voltage can be present at these terminals!
4 Digital
inputs
red
LED1
..
LED24
On: Digital input is activated
ATTENTION DANGER TO LIFE: External voltage can be present at these terminals!
Lower board
5 LIFE
green LED
top
Flashing: Active lamp, controller is supplied with power, processor is running
Off: Power supply interrupted or device defective
6 POWER green LED
bottom
On: Power supply OK
Off Power supply interrupted or device defective
6.4 Basic parameter settings
The parameters listed below must be adjusted in the corresponding operating screens of the controller:
Parameters
System configuration
(menu 3-1)
•
Sensor match
The pack controller operates with continuous pressure transmitters with linear characteristic curves. The
pressure inputs can be adjusted for various transmitters with linear characteristic curves. Transmitters
with both current output (4..20 mA) as well as with voltage output (0…10 V) can be used here.
Information for the precise terminal assignment can be found in chapter
..
For transmitters with voltage output, appropriate jumpers must be implemented on the controller
(see chapter
Konfiguration der analogen Ein- und Ausgänge
)! Analogue inputs in the pack
controller are preconfigured as current inputs (4..20 mA) at the factory.