Connection of the SIOX modules to the pack controller
The individual SIOX extension modules are supplied with power from the pack controller via the terminals 91-95
(SIOX-SUPPLY) and connected to each other in series via SIOX data cables (SIOX OUT and SIOX IN using
RJ45).
Example of a pack controller configuration with two SIOX extension modules:
SIOX power supply cables
•
Shielded cables with cross section > 0.5 mm
2
must be used for the 5 power supply cables (terminals
91-95). For example, the use of
LiYCY 4x0.75
mm
2
cables with 25 ohms/km is recommended.
•
Max. permitted cable length is 30 m.
•
The pack controller power supply is designed for the connection of a maximum of 3 extension modules.
SIOX data cables
•
The data cables (SIOX IN / SIOX OUT) should
not
be routed in the immediate proximity of high voltage
or high frequency cables.
•
When routing the cables, care must be taken to ensure that the minimum bending radius is complied
with and that the cables are not routed
parallel to cables
which have the potential to generate strong
interference coupling
.
•
Max. permitted data cable length is 30 m.
•
CAT5 cable or better must always be used.
Danger of destruction of components!
The connection of SIOX extension modules with each other
or to the controller may
only
be performed when no voltage is present! In the event of any mix-up of
the SIOX data cable (RJ45) with an Ethernet network cable with PoE (Power over Ethernet), involved
network devices can be damaged!