Terminal No. Function (0..10 V)
Base module
53
54
Speed controlled fan control
(for compressor step control)
or
Speed controlled compressor control
(for compressor combined control)
GND
+0..10 V
55
56
Medium pressure valve (MPV) control
GND
+0..10 V
57
58
High pressure valve (HPV) control
GND
+0..10 V
63
64
Speed controlled fan control
(for compressor combined control)
or
for the speed of the FC-controlled ECO compressor*
GND
+0..10 V
Malfunction due to interference!
All supply lines from and to the controller (with the exception of the
230 V power supply and signal lines) must be shielded (cable type LiYCY)! This particularly applies for
the analogue inputs and outputs (e.g. sensor supply cables) as well as the CAN bus cabling (see
Basics and General Safety and Connection Instructions
). As a general rule, care should be taken to
ensure that signal cables and cables carrying mains voltage are routed in separate cable channels.
* Special features for the analogue inputs:
1. If
connected to the Modbus are
actuated for the regulation. The analogue input 4 on the basic module is available for other
functions.