14.01.2019
89/185
DIP switch S1
Coding switch 1
Switch position Pack type
ON
Not used
OFF
Not used
Coding switches 2 and 3 setting - number of extension modules with manual control switch (number of
capacity stages)
DIP switch S1 coding switches 2 and 3 specify the maximum number of compressor and fan capacity stages.
The basic module can control 4 compressors and 4 fans.
An additional SIOX extension module is required for up to 8 compressor and 8 fan capacity stages; another
second SIOX extension module is required for up to 11 compressor and 12 fan capacity stages.
DIP switch S1
Coding switches 2 and 3
Switch position
Coding switch 2
Switch position
Coding switch 3
ON
ON
2 external SIOX extension modules
•
max. 11 compressor stages
•
max. 12 fans
ON
OFF
1 external SIOX extension module
•
max. 8 compressor stages
•
max. 8 fans
OFF
OFF
no SIOX extension module
•
max. 4 compressor stages
•
max. 4 fans
Coding switch 4 setting
DIP switch S1
Coding switch 4
Switch position
ON
Not used
OFF
Not used
Coding switch 5 setting
A maximum of 11 compressors and 12 fans can be used, see chapter
Содержание VS 3015 C
Страница 8: ...14 01 2019 8 185...