14.01.2019
163/185
VERD. ÜB POS:
XXXXX
Input Defa
ult
Di
m.
Verz.min_ÜH-V
XXX s
Alarm delay for minimum superheat of the pack (fault signal "Low superheat"")
1..30
10
s
Dif. ÜH XK
Hot gas bypass valve superheat difference (when the hot gas bypass function is activated) or
hysteresis for switching on the
suction gas injection valve (when the suction gas injection
function is activated):
Limit value = "Min. ÜH-K" + "Dif. ÜH" or
Limit value = "Min. ÜH-V" + "Dif. ÜH"
1..10
2
K
Ölausgl.zeit
Xm
Standstill time for oil balancing
2..9
2
Min
.