14.01.2019
140/185
SOLLWERTE POS: XXXXX
4 Refrigerant monitoring Continue to menu 3-4
5 External alarm
Continue to menu 3-5
6 Base load
Continue to menu 3-6
7 Messages
Continue to menu 3-7
8
-
9 Verfl.Überwach.
Continue to menu 3-9
•
Menu 3-1 System configuration
AUSBAU
POS: XXXXX
Input Def
ault
Di
m.
Kältemittel
R744
Refrigerant R744 (CO
2
)
-
R74
4
-
Sensor
match →
Matching of the pressure transmitters
→
Screen
3-1-b
Ölausgleich
sltg X
Block / enable oil equalisation YES/NO
Y/N
N
-
MD
Halteventil
Medium pressure holding valve available
YES/NO
Y/N
N
-
Heißgas-
Bypass
Hot gas bypass
available
JA/NEIN
Y/N
Y
-
Anz.Verdic
hter XX
Entry of the number of compressors
1..4/
8/12
4/8/
12
-
Ungl.Verd.
X
Unequal compressors (only visible for step control)
Y/N N
-
Anz.Verd.m
.LS XX
Entry of the number of compressors with capacity stages
0..6
0
-
Anz.LS pro
Verd. XX
Entry of the number of capacity stages / compressors
1..3
1
-
Ausg.LR
invert. X
Outputs of the capacity regulation inverted (if yes, the actuation of the relay outputs for the
compressor capacity stages is inverted. If necessary, coupling relays for the bypass valves can be
dispensed with)
Y/N N
-
Motorsch.
Verd. X
Enable motor overload cutout YES/NO
Y/N N
-
MotorschS
perre X
Enable motor overload interlock YES/NO (only visible if Motorsch. Verd. = YES)
Y/N Y
-