HD-REG
POS: XXXXX
Input Def
ault
Di
m.
P-Wert X.X
P-factor (amplification factor) for condenser fan speed control signal (only visible if speed
controller or combined control type of control has been selected - screen 3-2-2-1-a)
0.1..5.
0
1.0 -
P-Wert p
X.X
Pressure-dependent P-factor (amplification factor) for condenser fan speed control signal (only
visible if speed controller or combined control type of control has been selected - screen 3-2-2-1-a)
0.1..2.
0
0.0
-
-
I-Wert X.XX I-factor (integral factor) for condenser fan speed control signal
(only visible if speed controller or combined control type of control has been selected - screen
3-2-2-1-a)
0.00..
1.00
0.03 -
Intervall I
XX s
Time interval for calculation of I-component for condenser fan speed control signal (only visible if
speed controller or combined control type of control has been selected - screen 3-2-2-1-a)
1..60 10
s
Offset XX% Offset for condenser fan speed correcting variable (only visible if the speed controller or combined
control type of control has been selected - screen 3-2-2-1-a)
1..50 10
%
Switch
mode
→
Condenser fan control / star-delta operation switch mode (only visible if step controller type of
control has been selected - screen 3-2-2-1-a)
→
Screen
3-2-2-1-d
Gr. Drehz.
N X
High speed (delta operation) also permitted for night setpoint Y/N (only visible if step controller
type of control (screen 3-2-2-1-a) has been selected and parameter
Schaltart
KKGG or KKKG has
been selected (screen 3-2-2-1-b)
Y/N
Y
-
Verz.kl.Dre
hz. XX s
Delay of loading a condenser fan stage in star operation after it has been unloaded from delta
operation (only visible if
step controller
type of control (screen 3-2-2-1-a) has been selected and
Schaltart
KKGG or KKKG has been selected (screen 3-2-2-1-b)
0..30 5
s
tG-Max
XX°C
Max. gas cooler outlet temperature for switching to power supply bridging
---,
25..56
28
-
-
Lü.mit
Verd.AUS X
Switch off condenser fans with compressors YES/NO
Y/N
N
-
Lü.bei
Stör.AUS X
Switch off condenser fans when motor overload cutout is tripped YES/NO
Y/N
Y
-
Übw.bei.Lü.
AUS
Condenser fans are not monitored for their motor protection in standstill.
Y/N
Y
-
Lü.bei
Byp.AUS
A GLT controller activates the gas cooler bypass. This is signalled to the pack controller via CAN
bus. If the parameter is set to Y, all condenser fans in this operating state are switched off.
Y/N
N
-
Lü.scan
Tausch
"Partial Search": only new condenser fans added to the Modbus are searched for here, e.g. in the
case of replacement of a defective condenser fan.
Condition: the new condenser fan must have the Modbus address 1 (factory setting). If this is not
the case, the "Manual Search" (recommended) or the "Complete Search" must be performed
Y/N
N
-
Lü.scan
NEU
"Complete Search": all fans on the Modbus are searched for and reconfigured (recommended for
initial commissioning)
Note: the configuration of the switching order is lost for the complete search and must be
checked / defined.
Only visible if authorisation = Master
Y/N
N
-