Firmware V3.15
21.04.2021
116/401
7.7 Terminal assignment of the CAN bus terminals
For further details about the setting of the CAN bus address see chapter
.
Controller type
Terminal No.
CAN bus
Wire colour
All controllers
1
Shield (SHLD)
Shield
2
CAN-GND
green
3
CAN-LOW
brown
4
CAN-HIGH
white
Warning about dangerous electrical voltage!
If mains voltage is connected to the CAN bus terminals, this will result in the destruction of all
components connected to the CAN bus!
All supply lines from and to the case controller, particularly those of the CAN bus, must be shielded
(cable type: LiYCY)! As a general rule, care should be taken to ensure that signal cables and cables
carrying mains voltage are routed in separate cable channels.
The orange CAN bus LED always flashes when data are being exchanged via the CAN bus with the
system centre / store computer; see chapter
Содержание UA 400
Страница 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1 ...
Страница 133: ...Firmware V3 15 21 04 2021 133 401 Upper case and lower case can be toggled by tapping the MODE button ...
Страница 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD ...
Страница 244: ...Firmware V3 15 21 04 2021 244 401 ...
Страница 324: ...Firmware V3 15 21 04 2021 324 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint ...
Страница 357: ...Firmware V3 15 21 04 2021 357 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint ...
Страница 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay ...
Страница 372: ...Firmware V3 15 21 04 2021 372 401 ...