• Menu 6-5 Alarm priorities
ALARMPRIOS POS: XXXXX
Entry
Default
Prio.Refrig. Pt. X
Global alarm priority by refrigeration point
priority (Menu 6-1) (Y)
,
,
(Y,N)
N
Priority: XX
Show refrigeration point priority (Menu 6-1)
Only shown when refrigeration point priority
set to Y.
2
Following parameters are only shown when
refrigeration point priority is set to N. Meaning of
usable entries for alarm priority:-= Event ignored
0=Message (entered only in message log)
1=Priority 1 alarm..99=Priority 99 alarm
Low Temp.
Temperature below lower alarm limit
Priority applies to following alarms:
Low Temp. Zone1, Low Temp. Zone2
-, 0..99
2
High Temp.
Temperature above upper alarm limit
Priority applies to following alarms:
High Temp. Zone1, High Temp. Zone2
-, 0..99
1
Sensor Fault
Temperature sensor failure
-, 0..99
2
No Defrost
No defrost within alarm delay interval
Priority applies to following alarm: No
defrost
-, 0..99
2
Timer-Term.Defr.
Defrosting terminated by safe defrost time
-, 0..99
0
Power Failure
Start following power failure
-, 0..99
0
First Start
Controller start up (basic settings loaded!)
-, 0..99
2
Manual Shutoff
Manual switch Input D31/D32 set OFF
-, 0..99
0
Hardware Fault
Internal hardware fault
Priority applies to following alarms:
EEPROM Fault, RTC Fault, Flash Fault
-, 0..99
1
Setpoint Change
Message generated on changing setpoint
0..99
0
Refrig.Pt.Dis.
Cooling by pack controller via CAN bus
interrupted
-, 0..99
0
Battery Voltage
Battery low
-, 0..99
0
Содержание UA 400
Страница 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1 ...
Страница 133: ...Firmware V3 15 21 04 2021 133 401 Upper case and lower case can be toggled by tapping the MODE button ...
Страница 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD ...
Страница 244: ...Firmware V3 15 21 04 2021 244 401 ...
Страница 324: ...Firmware V3 15 21 04 2021 324 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint ...
Страница 357: ...Firmware V3 15 21 04 2021 357 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint ...
Страница 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay ...
Страница 372: ...Firmware V3 15 21 04 2021 372 401 ...