• Menu 6-5 Alarm priorities
ALARMPRIOS POS: XXXXX
Entry
Default
Prio.Refrig. Pt. X
Global alarm
priority by
refrigeration point
priority (Menu
6-1) (Y)
,
, (Y,N)
N
Priority: XX
Show
refrigeration point
priority (Menu
6-1)
Only shown when
refrigeration point
priority set to Y.
Following parameters are only shown when refrigeration
point priority is set to N. Meaning of usable entries for
alarm priority:-=Event ignored0=Message (entered only in
message log) 1=Priority 1 alarm..99=Priority 99 alarm
Low Temp.
Temperature
below lower alarm
limit
Priority applies to
following alarms:
Low Temp.
Zone1, Low
Temp. Zone2
-, 0..99
2
High Temp.
Temperature
above upper
alarm limit
Priority applies to
following alarms:
High Temp.
Zone1, High
Temp. Zone2
-, 0..99
1
Sensor Fault
Temperature
sensor failure
-, 0..99
2
No Defrost
No defrost within
alarm delay
interval
Priority applies to
following alarm:
No defrost
-, 0..99
2
Timer-Term.Defr.
Defrosting
terminated by
safe defrost time
-, 0..99
0
Power Failure
Start following
power failure
-, 0..99
0
First Start
Controller start up
(basic settings
loaded!)
-, 0..99
2
Manual Shutoff
Manual switch
Input D31/D32 set
OFF
-, 0..99
0
Содержание UA 400
Страница 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1 ...
Страница 133: ...Firmware V3 15 21 04 2021 133 401 Upper case and lower case can be toggled by tapping the MODE button ...
Страница 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD ...
Страница 244: ...Firmware V3 15 21 04 2021 244 401 ...
Страница 324: ...Firmware V3 15 21 04 2021 324 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint ...
Страница 357: ...Firmware V3 15 21 04 2021 357 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint ...
Страница 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay ...
Страница 372: ...Firmware V3 15 21 04 2021 372 401 ...