Firmware V3.15
21.04.2021
84/401
The following controller types can be set using the DIP switch S3:
Controller type or master / slave mode
DIP switch S3 (switch positions of the coding switches 1 .. 9)
1
2
3
4
Master /
Slave mode
5
6
7
8
9
Nor
mal
Ope
rati
on /
Fir
mw
are
Upd
ate
(onl
y
2nd
gen
erat
ion
con
troll
ers)
Case controller
UA 111
OFF
OFF
OFF
ON/OFF
OFF
OFF
OFF
OFF
ON
UA 111 D
OFF
ON
ON
ON/OFF
OFF
OFF
OFF
OFF
ON
UA 121
ON
OFF
OFF
ON/OFF
OFF
OFF
OFF
OFF
ON
UA 131 without
fan control
UA 131 with fan
control
(terminals 73/74)
OFF
ON
OFF
ON/OFF
OFF
ON
OFF
OFF
OFF
ON
UA 131 LS with
enhanced fan
control
(terminals
15/16/18)
ON
ON
ON
ON/OFF
ON
OFF
OFF
OFF
ON
UA 131 DD
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
ON
UA 141
ON
ON
OFF
ON/OFF
OFF
OFF
OFF
OFF
ON
Cold room controller
UR 141 NK
OFF
OFF
ON
ON/OFF
OFF
OFF
OFF
OFF
ON
UR 141 TK
ON
OFF
ON
ON/OFF
OFF
OFF
OFF
OFF
ON
* Enable of special functions. Information about whether the DIP switch 8 must be set to ON can be found for
the corresponding functions in the chapter
. After the DIP switch 8 has been
changed, a controller restart must always be performed, otherwise the setting will not be adopted.
Due to the setting of the controller type, only a part of the functions and parameters of the case controller is
always available.
In the case of any setting of coding switch combinations that are not present in the list, UA 131 is automatically
applied as controller type and an alarm message is created.
Содержание UA 400
Страница 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1 ...
Страница 133: ...Firmware V3 15 21 04 2021 133 401 Upper case and lower case can be toggled by tapping the MODE button ...
Страница 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD ...
Страница 244: ...Firmware V3 15 21 04 2021 244 401 ...
Страница 324: ...Firmware V3 15 21 04 2021 324 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint ...
Страница 357: ...Firmware V3 15 21 04 2021 357 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint ...
Страница 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay ...
Страница 372: ...Firmware V3 15 21 04 2021 372 401 ...