Firmware V3.15
21.04.2021
76/401
6.1.1 DIN rail mounting of the case/cold-room controller
Similar to illustration
The case controller is attached to the DIN rail (35 mm) using two retaining springs. The DIN rail must have a
minimum height of 5 mm.
The power loss of the device is approx. 11 VA and must be taken into account for the installation.
The case controller may only be mounted on a Cap (DIN) rail and operated as an integrated regulation
and control device (EN60730). All leads running to and from the case controller - especially those of
the CAN bus - must be shielded (cable type: LiYCY)! No shielding is required on sensor leads when
installed exclusively inside the refrigerated display case and when external interference (for example
from parallel power wires) is not to be expected (see operating instruction "Introduction, General Safety
and Connection Instructions"). As a general rule, care should be taken to ensure that signal leads and
leads carrying a supply voltage are routed through separate cable channels.
Electrical enclosure and dimensions are listed in Section
Содержание UA 400
Страница 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1 ...
Страница 133: ...Firmware V3 15 21 04 2021 133 401 Upper case and lower case can be toggled by tapping the MODE button ...
Страница 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD ...
Страница 244: ...Firmware V3 15 21 04 2021 244 401 ...
Страница 324: ...Firmware V3 15 21 04 2021 324 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint ...
Страница 357: ...Firmware V3 15 21 04 2021 357 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint ...
Страница 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay ...
Страница 372: ...Firmware V3 15 21 04 2021 372 401 ...