Firmware V3.15
21.04.2021
160/401
•
9.1.7 Menu 6 Configuration UA 111
KONFIGURAT POS: XXXXX
1 Refrigeration point
Continue to menu 6-1
2 Controller
Continue to menu 6-2
3 Cooling
Continue to menu 6-3
4 Language
Continue to menu 6-4
5 Alarm Priorities
Continue to menu 6-5
6 Emergency power operation
Continue to menu 6-6
7 Advanced
Continue to menu 6-7
Menu 6-1 - Refrigeration point
KÜHLSTELLE POS:
XXXXX
Input
Default
Refr. Pt. Name:
Only text
xxxxxxxxxxxxxxx
Free text that designated the refrigeration point
(see note after the table)
Case controller
Position: XXXXX
Free text that is displayed in the menu after
position (POS) (see note after the table)
UA400
Priority: XX
Priority of the alarms for refrigeration point failure
or setting of the global controller priority (menu
6-5)
,
, or numbers (0..99)
1
Verbund Nr.: XX
Number of the pack controller that the case
controller is assigned to
,
, or numbers (--,
1..9)
1
Verbundsatz: XXX
Membership of a compressor pack;
This parameter is only required for coupling to a
VS 3010 BS with multiple zones. This parameter
must be disabled (--) if any other type of pack
controller is used.
,
, or numbers (---, Z1,
Z2)
—
Temperaturzonen X
Number of temperature zones
Single-zone operation
Two-zone operation
,
, or numbers (1, 2)
2
Fühleranzahl XX
Display of the connected temperature sensors
After input of
, a sensor scan is performed,
during which the number of sensors is
determined again.
The priority for older versions of the store computer (< V5.0) may only be allocated in the range 0..2;
see
chapter
10.1 Alarm signalling and monitoring
Alarm signalling / individual allocation of the priorities.
Содержание UA 400
Страница 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1 ...
Страница 133: ...Firmware V3 15 21 04 2021 133 401 Upper case and lower case can be toggled by tapping the MODE button ...
Страница 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD ...
Страница 244: ...Firmware V3 15 21 04 2021 244 401 ...
Страница 324: ...Firmware V3 15 21 04 2021 324 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint ...
Страница 357: ...Firmware V3 15 21 04 2021 357 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint ...
Страница 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay ...
Страница 372: ...Firmware V3 15 21 04 2021 372 401 ...