Firmware V3.15
21.04.2021
389/401
No.
Message
Cause
Correction
127
Manual Shutoff
Manual Shutdown
digital input actuated.
-
128
Sensor Fault Fx
Sensor fault! Sensor disconnected, short-circuited
or corrupted by external interference. Temperature
on sensor outside set measuring range. Monitoring
is performed on required or optional sensors
recognized by controller as result of sensor scan.
Check connecting cable, Check cable
shielding or
Replace sensor(s) concerned: F1..F9 =
Terminal /Z12..Z91/92F10 = Terminal Z01/Z02
Sensor Fault A1, A2
The message "Sensor fault A1/A2" appears when
in menu 6-2-6 the parameter "AIN1" and "AIN2" of
the analogue inputs are set to "Active=Yes" but no
sensor is recognized. Note: A1/A2 = Analog input
AIN1/AIN2
Check connecting cable, Check cable
shielding ,Replace sensor(s) concerned or set
the parameter „AIN1" resp. AIN2" in the menu
6-2-6 to „AIN1/2 activ=no"
189
Refrig. Pt. Disabl.
Refrigeration point enabling disabled.
-
240
Setpoint Change
Setpoint changed.
-
Содержание UA 400
Страница 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1 ...
Страница 133: ...Firmware V3 15 21 04 2021 133 401 Upper case and lower case can be toggled by tapping the MODE button ...
Страница 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD ...
Страница 244: ...Firmware V3 15 21 04 2021 244 401 ...
Страница 324: ...Firmware V3 15 21 04 2021 324 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint ...
Страница 357: ...Firmware V3 15 21 04 2021 357 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint ...
Страница 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay ...
Страница 372: ...Firmware V3 15 21 04 2021 372 401 ...