Firmware V3.15
21.04.2021
98/401
•
•
•
•
•
Step 2:
The PC must be restarted after the installation process:
* Further information:
USB cable: see chapter
Installation program & firmmware: see
https://edp.eckelmann.de/edp/lds/_NbH4owBiFn
Tips for
Rectification of driver problems
6.6.2 Installing firmware update
When installing the firmware update, a distinction is made between two device generations:
2nd generation controller (from Oct./Nov. 2018)
Characteristic: 9-pole DIP switch
1st generation controller (since 2011)
Characteristic: 8-pole DIP switch
6.6.2.1 Update for controller with 9-pole DIP switch
Controller characteristic: 9-pole DIP switch
The settings depend on the controller type!
Step 1: Set DIP switch S3 and connect controller to PC
No
error message such as "
USB device not found
" should be displayed on the laptop or PC. *
The steps described in the chapter
Voraussetzungen für das Firmware-Update
performed once for each PC in order to perform a successful firmware update.
Содержание UA 400
Страница 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1 ...
Страница 133: ...Firmware V3 15 21 04 2021 133 401 Upper case and lower case can be toggled by tapping the MODE button ...
Страница 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD ...
Страница 244: ...Firmware V3 15 21 04 2021 244 401 ...
Страница 324: ...Firmware V3 15 21 04 2021 324 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint ...
Страница 357: ...Firmware V3 15 21 04 2021 357 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint ...
Страница 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay ...
Страница 372: ...Firmware V3 15 21 04 2021 372 401 ...