Firmware V3.15
21.04.2021
90/401
6.
Select menu
6 Configuration – 3 Cooling
.
6 Configuration - 3 Cooling
KÜHLUNGPOS: XXX
Korroff. to XXK
Correction offset which is applied to the t 0 actual value received from the pack
controller via CAN bus. This enables pressure losses in the refrigerant line to be
compensated. If this value is set to "–", the case controller regulates using the
temperature sensors at the evaporator input and output (standalone operation).
Dauerl.Überw. XXm
Continuous use monitoring
DG-Betrieb AUS
This must be set for UA 131 E to guarantee that the D2D defrost runs correctly. The
defrost timer should be set to EXT when activating this operating mode.
Lüfterverzöger XX°C
Maximum value at the defrost sensor, at which the fan should be switched on after a
delay (e.g. after the defrost)
7.
Exit the
Configuration
menu by tapping the
ESC
button twice and select
3 Clock – 2 Defrost timer
Input of the relevant parameters in the following screen.
3 Clock - 2 Defrost Timer
ABTAUUHRPOS: XXX
AbtauuhrINT
Selection of defrost using external or internal defrost timer
Sicherheitsz.60m
Safe defrost time; the defrost is not longer than this time.
Defrost 1 DD-DD hh:mm
Entry of defrost times
Defrost 2 DD-DD hh:mm
...
Defrost 14 DD-DD hh:mm
man. AbtauungAUS
Manual defrost ON/OFF
8.
Exit from the
2 Defrost Timer
menu by tapping the
ESC
button.
9.
Select menu
3 Toggle Setpoint
, input of the relevant parameters in the following screen:
3 Clock - 3 Toggle Setpoint
UMSCHALTNGPOS: XXX
StatusAUS
Only visible if Sollumschaltg. is set to INT or EXT
Sollumschaltg.EXT
Selection INT, EXT, --: internal, external, deactivated toggle setpoint
Selection
INT: internal
EXT: external
--: deactivated toggle setpoint
Laufzeit Rollo0s
Input operating time of the blind of the multidecks
Um EIN: DD-DD hh:mm
Input time for toggle setpoint
(only visible if Sollumschaltg. is set to INT)
Содержание UA 400
Страница 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1 ...
Страница 133: ...Firmware V3 15 21 04 2021 133 401 Upper case and lower case can be toggled by tapping the MODE button ...
Страница 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD ...
Страница 244: ...Firmware V3 15 21 04 2021 244 401 ...
Страница 324: ...Firmware V3 15 21 04 2021 324 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint ...
Страница 357: ...Firmware V3 15 21 04 2021 357 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint ...
Страница 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay ...
Страница 372: ...Firmware V3 15 21 04 2021 372 401 ...