Firmware V3.15
21.04.2021
89/401
4.
Exit from the menu
1 Refrigeration point
by tapping the
ESC
button once and select menu
6 Configuration
- 2 Controller
.
6 Configuration - 2 Controller
REGLERPOS: XXX
1 Type and version
Type, serial number and Master / Slave (ON/OFF)
2 Temperature display
Adjustment of the displayed temperature value
3 Alarm delay
Input of an alarm delay time
4 230 V inputs
230 V inputs
5 Sensor type
Selection of the temperature sensor of the type L243, K277 or 5K3A1
5.
Select menu
6 Configuration - 2 Controller
-
3 Alarm delay
.
6 Configuration – 2 Controller – 3 Alarm delay.
ALARMVERZ.POS: XXX
Fühlerbruch XXm
Alarm delay for sensor fault
Über/Unter Tmp XXXm
Alarm delay for high temperature or low temperature
keine Abtauung XXXh
Alarm is tripped if no defrost is performed within this configurable time.
SelbsthaltungN
NO: Automatic reset of non-transient alarms
YES: Alarms must be reset manually
Exit the menu by tapping the
ESC
button once.
Risk of failure of alarm messaging in the event of problems!
Alarms can be suppressed if the
alarm priority is set to 0. The value of the suction pressure for the control functions is not available to
the case controller
until after
the pack number of the associated pack controller has been selected on
the case controller.
Risk of damage to the system and stock loss!
It must be strictly ensured that the correct pack
number is set, otherwise this can result in damage to the installation or stock. The setting can be
checked at Refrigeration point - 1 Actual values - 1 Temperature sensors. The value
t
0
VS korr.
displayed there is the offset corrected t actual value of the pack controller as indicated in the pack
number field. In standalone operation via the local pressure transmitter, the pack number and the
parameter
t
0
VS korr.
only have any meaning if the signal from the pressure transmitter is not
available. In this case, the controller attempts to replace the missing signal with a pressure value
measured at the pack controller and transmitted via the CAN bus (if available).
A sensor scan (Menu 6-1)
must
be performed during commissioning or after a first start! The sensor
scan is the only possibility to define the sensors to be monitored; see
chapter
Содержание UA 400
Страница 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1 ...
Страница 133: ...Firmware V3 15 21 04 2021 133 401 Upper case and lower case can be toggled by tapping the MODE button ...
Страница 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD ...
Страница 244: ...Firmware V3 15 21 04 2021 244 401 ...
Страница 324: ...Firmware V3 15 21 04 2021 324 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint ...
Страница 357: ...Firmware V3 15 21 04 2021 357 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint ...
Страница 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay ...
Страница 372: ...Firmware V3 15 21 04 2021 372 401 ...