Firmware V3.15
21.04.2021
38/401
•
•
•
•
5.5.3 Discharge gas defrosting (hot gas defrosting)
Discharge gas defrosting involves feeding discharge gas into the evaporator and can be performed with either
hot or cold gas.
The discharge gas is supplied from a point upstream of the condenser (hot gas defrosting) or from the receiver
downstream of the condenser (cold gas defrosting).
These notes apply to two-pipe discharge gas defrosting. In doing so, the defrost relays are used for the
actuation of special solenoid valves for the discharge gas defrosting. In discharge gas defrosting allowance is
made for the specific properties of the discharge gas:
Demand defrost counter ignored on initiation of defrosting
No internal initiation of defrosting
No interruption of defrosting in occurrence of temperature alarm
Discharge gas defrosting requires a pack controller in the system. Case controllers which participate in the
hot gas defrosting must be assigned to a pack controller using the parameter
Refr.Sys.No.
. The
parameter
Refr.Sys.Type
must also be set for VS 3010 BS pack controllers. No further parameters have to
be set here.
Activating discharge gas defrosting on UR 141 TK (LT):
Discharge gas defrosting is always active on the UR 141 TK (LT) and does not require any further parameter
setting.
Termination of discharge gas defrosting on UA 131 DD:
Defrosting is terminated by the defrost termination temperature sensors at the earliest 4 minutes after defrost
initiation.
Termination of discharge gas defrosting on UR 141 TK (LT):
Defrosting is terminated by the defrost termination temperature sensors without delay. If an internal defrost
timer is set on the UA 141 TK (LT), it will be changed automatically to external defrosting by the pack controller
the first time discharge gas defrosting is initiated. This prevents the case controller from automatically initiating
defrosting.
Compressor damage!
Danger due to liquid refrigerant on the suction side of the compressor!
Discharge gas defrosting
as described herein is D2D two-pipe discharge defrosting, which can be performed only with hot gas.
Notes on discharge gas defrosting (controller type UA 131 DD, UR 141 TK (LT))
Compressor damage!Danger due to liquid refrigerant on the suction side of the
compressor!
During the first start of the UA 131 a defrosting is initiated immediately following the
start. If the installation is not secured with suitable pack controller control lines for initiating the
discharge gas defrosting, liquid refrigerant can e.g. enter the suction hose. Therefore care must be
taken with applications with discharge gas defrosting that the manual defrost is deactivated following
the start of the controller and that the defrost timer is set to external defrost. Alternatively, i.e. in
addition, the activation of the regulator control elements specific to the discharge gas can be secured
using suitable control lines, e.g. from the pack controller.
Discharge gas defrosting cannot be used together with the master-slave function. With discharge gas
defrosting the operation must be terminated when the CAN bus defrost command ends. With master-
slave defrosting the operation would normally continue until the safe defrost time expires.
Содержание UA 400
Страница 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1 ...
Страница 133: ...Firmware V3 15 21 04 2021 133 401 Upper case and lower case can be toggled by tapping the MODE button ...
Страница 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD ...
Страница 244: ...Firmware V3 15 21 04 2021 244 401 ...
Страница 324: ...Firmware V3 15 21 04 2021 324 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint ...
Страница 357: ...Firmware V3 15 21 04 2021 357 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint ...
Страница 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay ...
Страница 372: ...Firmware V3 15 21 04 2021 372 401 ...