Firmware V3.15
21.04.2021
99/401
Before
starting the firmware update, only coding switch 9 of the DIP switch S3
must
be set to
OFF
:
Connect the controller to the PC via a USB A-B cable while
disconnected from the power supply
:
then supply the controller with power again, see chapter
Terminal assignment for 230 V AC power supply
Step 2: Perform firmware installation
Under "
Start / Programs / ECKELMANN / Firmware Uploader
", start the program "
KGL Firmware Uploader
".
The following window opens:
Click the "Find Controller" button to find the controller.
Practical tip:
The original position of the coding switches 1..9 of the DIP switch S3 should be
documented, e.g. with a mobile telephone photo.
After
the firmware update has been performed, the coding switch 9 of DIP switch S3 must be
reset to
its original position
.