Firmware V3.15
21.04.2021
164/401
•
•
The value is selected in accordance with the entry. The check mark indicates the current setting.
FÜHLERTYP POS: XXXXX
Input
Default
L243
Temperature range -50..50 °C
K277
Temperature range -50..50 °C
5K3A1
Temperature range 0..100°C
Menu 6-3 Cooling
KÜHLUNG POS: XXXXX
Input
Default
min. Laufzeit XX K
Minimum run time of the cooling
0..15
2 m
min. Standzeit XX m
Minimum switch-off time of the cooling
0..15
2 m
Dauerl.überw. XX m
Time for the forced interruption of the cooling during
continuous operation
--, 0..15
0 m
Notbetrieb XX m
If necessary sensors for the regulation fail, the
solenoid valve is actuated with the opening degree in
[%]set here.
0..100
40%
Menu 6-4 - Language
SPRACHE POS: XXXXX
Input
Default
Deutsch D
English GB
Français F
Espagnol E
Finnish FIN
Türkce TR
Cesky CZ
Содержание UA 400
Страница 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1 ...
Страница 133: ...Firmware V3 15 21 04 2021 133 401 Upper case and lower case can be toggled by tapping the MODE button ...
Страница 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD ...
Страница 244: ...Firmware V3 15 21 04 2021 244 401 ...
Страница 324: ...Firmware V3 15 21 04 2021 324 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint ...
Страница 357: ...Firmware V3 15 21 04 2021 357 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint ...
Страница 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay ...
Страница 372: ...Firmware V3 15 21 04 2021 372 401 ...