Firmware V3.15
21.04.2021
215/401
•
•
•
•
•
Menu 3-2-a Def.Tim.Z2
DEFR.TIMER POS: XXXXX
Entry
Default
Defrost Timer XXX
Setting for how temperature zone 2 should
defrost:- MitZ1 Together with zone 1- INT
Internally- EXT Externally – the defrost of both
temperature zones is started simultaneously via
the external signal
,
,
(ViaZ1(ViaZ1,EXT,INT)
ViatZ1
Safe Defr Time XXX m
Safe defrost time, i.e. max. allowed duration of
defrosting (internal defrost only)
0..120
60 min
Manual Defrost XXX
Status (ON/OFF) of auxiliary manual defrost *)
,
, (ON/OFF)
OFF
Defr. 1 xxxxx hh:mm
Defrost start time for internal defrost; weekday,
time of day; shown only when parameter
defrost
timer
= INT
,
, (Mo-Su) or numbers
(hh:mm)
Mo-Su 01:00
...
Defr. 14 xxxxx hh:mm
Menu 3-3 Toggle Setpoints
TOGGLE POS: XXXXX
Entry
Default
Status XXX
Setpoint toggle status (OFF/ON) of alternative
set of setpoints (setpoint toggle)
Toggle Setp. XXX
Setpoint toggle via
EXT digital input D21/22
INT internal timer
CAN bus- „--" deactivated
,
, (EXT, INT, CAN, --)
EXT
Blind On Time X s
Fan and cooling stop time after toggling to
alternative set of setpoints with external setpoint
toggle (Menu 3-3)
0..250
50 sec
Alt
ON: DD-DD hh:mm
Start time for toggle to alternative set of setpoints
Weekday from - to XXXXX, time hh:mm
Only shown when internal setpoint toggle is
activated (Menu 3-3)
,
, (Mo-Su etc.) or
numbers (hh:mm)
Mo-Su
21:00
Alt
OFF: DD-DD hh:mm
End time for toggle to alternative set of setpoints
Weekday from - to XXXXX, time hh:mm
Only shown when internal setpoint toggle is
activated (Menu 3-3
,
, (Mo-Su etc.) or
numbers (hh:mm)
Mo-Su
05:00
Alt
ON: DD-DD hh:mm
Start time for toggle to alternative set of setpoints
Weekday from - to XXXXX, time hh:mm
Only shown when internal setpoint toggle is
activated (Menu 3-3)
,
, (Mo-Su etc.) or
numbers (hh:mm)
Su
05:00
*) Parameter automatically set to ON for safe defrost time at first start.
Содержание UA 400
Страница 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1 ...
Страница 133: ...Firmware V3 15 21 04 2021 133 401 Upper case and lower case can be toggled by tapping the MODE button ...
Страница 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD ...
Страница 244: ...Firmware V3 15 21 04 2021 244 401 ...
Страница 324: ...Firmware V3 15 21 04 2021 324 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint ...
Страница 357: ...Firmware V3 15 21 04 2021 357 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint ...
Страница 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay ...
Страница 372: ...Firmware V3 15 21 04 2021 372 401 ...