Firmware V3.15
21.04.2021
77/401
6.1.1.1 Mounting on the DIN rail
Step 1:
The two retaining springs on the underside of the device must be pulled out using a flat-blade
screwdriver until they click into place.
Warning about dangerous electrical voltage! Danger of electric shock!
The safety instructions and
work safety instructions
must
be observed for the mounting.
All
plug connectors may only be inserted
and removed when the power supply is disconnected.
In order to carry out the assembly / dismantling, there must be a distance of at least 8 mm from the
next component (e.g. cable duct), otherwise the retaining springs cannot be pulled out.