Firmware V3.15
21.04.2021
348/401
ALARMPRIOS POS: XXXXX
Entry
Default
Manual Shutoff
Manual switch
Input D31/D32 set
OFF
-, 0..99
0
Hardware Fault
Internal hardware
fault
Priority applies to
following alarms:
EEPROM Fault,
RTC Fault, Flash
Fault
-, 0..99
1
Setpoint Change
Message
generated on
changing setpoint
0..99
0
Refrig.Pt.Dis.
Cooling by pack
controller via CAN
bus interrupted
-, 0..99
0
Battery Voltage
Battery low
-, 0..99
0