4. "Delay after the defrost" operating mode
The fan relay is switched on continuously during the cooling in this operating mode. The fan relay switches off
at the start of a defrost. The fan relay remains switched off during the defrost. When the defrost is finished, the
fan relay switches on again if the parameter
Lüfterverzöger
on the evaporator is undercut again.
In single-zone operation, only the evaporator sensor R1.1 has to fall below the value of
Lüfterverzöger
so that
the fan relay is switched on.
In two-zone operation, both evaporator sensors R1.1
and
R1.3 must fall below the value of
Lüfterverzöger
so
that the fan relay is switched on again. If the evaporator sensor R1.3 is not attached, then the fan relay is also
only controlled via R1.1 in two-zone operation.
The fan relay is switched off during any possibly parametrised wait or drip time. The parameter
Lüfter
Über
has no effect in this operating mode.
Содержание UA 400
Страница 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1 ...
Страница 133: ...Firmware V3 15 21 04 2021 133 401 Upper case and lower case can be toggled by tapping the MODE button ...
Страница 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD ...
Страница 244: ...Firmware V3 15 21 04 2021 244 401 ...
Страница 324: ...Firmware V3 15 21 04 2021 324 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint ...
Страница 357: ...Firmware V3 15 21 04 2021 357 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint ...
Страница 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay ...
Страница 372: ...Firmware V3 15 21 04 2021 372 401 ...