Firmware V3.15
21.04.2021
274/401
•
•
Menu 2-6-1 hot gas
HOTGAS POS: XXXXX
Entry
Default
Fans Start
Fan start setpoint
--, -20 .. 20
-5 °C
Flooding Evap.
Evaporator flood duration
0..15
3 m
Menu 2-6-1 Hot gas U
HOTGAS A POS: XXXXX
Entry
Default
Fans Start
Fan start setpoint
--, -20 .. 20
-5 °C
Flooding Evap.
Evaporator flood duration
0..15
3 m
Содержание UA 400
Страница 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1 ...
Страница 133: ...Firmware V3 15 21 04 2021 133 401 Upper case and lower case can be toggled by tapping the MODE button ...
Страница 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD ...
Страница 244: ...Firmware V3 15 21 04 2021 244 401 ...
Страница 324: ...Firmware V3 15 21 04 2021 324 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint ...
Страница 357: ...Firmware V3 15 21 04 2021 357 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint ...
Страница 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay ...
Страница 372: ...Firmware V3 15 21 04 2021 372 401 ...