Execution i.e. sequence of the defrost sequence
A defrost is initiated on the master controller for the defrost sequence (DS master).
The DS master initiates a defrost of all the DS slaves in group 1. If there are no DS slaves with the group
number 1, then the DS master defrosts alone. All the controllers (DS slaves) with other DS group numbers
continue to operate in their normal cooling mode.
If the defrost termination temperature is reached by
all
the controllers of the DS group or their safe defrost
times have elapsed, then the DS master initiates a defrost for the next highest DS group number.
If a delay time "
DS-Wait time
" (menu 2-2-1, i.e. menu 2-2-2) has been parameterized then the start of the
defrost sequence for the subsequent DS group is delayed accordingly.
The defrosts are continued until the entire chain of controllers has been run through. The defrost sequence is
now finished and all controllers have resumed cooling.
Configuration / parameterization of defrost sequence
The defrost is parameterized in menu 2 – Setpoints – 2 Defrost Zone 1.
The first thing to be configured is the function of the controller with respect to the defrost sequence (master or
slave, i.e. OFF if the controller is not to participate in the defrost sequence, parameter "
DS-Function
").
In the case of the slaves the corresponding DS group (parameter
DS-Group
) and the CAN bus address of the
DS master (parameter
DS-Master
) must be set. The DS master is automatically in DS group 1, if it is set to a
different group this has no effect on the master. Furthermore, the delay time between two group defrosts must
be set on the DS master.
Example: Configuration of a defrost sequence
Start of defrost
In the case of the DS master controller a defrost is activated via the internal clock, the external contact or via
manual defrost (CAN/local).
Configuration of the group members
With respect to the parameter
"DS-Function
", the DS master must be set to "Master". The parameter "
DS-Wait
time
" specifies the delay time in minutes which the DS master maintains between the defrosting of two groups.
The delay time applies unchanged across all groups.
The parameters "
DS-Group
" and "
DS-Master
" are ignored by the DS master and should be set to "--".
With respect to the parameter "
DS-Function
", the DS slaves must be set to "Slave".
On the slaves the parameter "
DS-Group
" must be set so that the controller is defrosted in the desired group
with other controllers and/or in the desired sequence relative to other controllers. For purposes of clarity, the
group numbers should be assigned in ascending order and without omissions along with the CAN bus address,
however this is not obligatory.
With the parameter "
DS-Master
" the CAN bus address of the DS master is set for every slave. This specifies
which of the controllers coordinates/executes the defrost. The parameter "
DS-Wait time
" is ignored by the DS
slave and should be set to "-". Similarly, the parameters for the defrost timer should be configured so that no
additional defrosts occur on the slave if no additional defrosts are desired outside of the defrost sequence. To
this end, it is recommended to set all the defrost times to "-" and the parameter "
Defrost Timer
" to "INT" (menu
3-2).
The DS master
always
belongs to DS group 1!
Содержание UA 400
Страница 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1 ...
Страница 133: ...Firmware V3 15 21 04 2021 133 401 Upper case and lower case can be toggled by tapping the MODE button ...
Страница 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD ...
Страница 244: ...Firmware V3 15 21 04 2021 244 401 ...
Страница 324: ...Firmware V3 15 21 04 2021 324 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint ...
Страница 357: ...Firmware V3 15 21 04 2021 357 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint ...
Страница 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay ...
Страница 372: ...Firmware V3 15 21 04 2021 372 401 ...