Firmware V3.15
21.04.2021
263/401
•
9.5.2 Menu 1 Actual Values UA 131 DD
ACT VALUES POS: XXXXX
1 Temp. Sensor
Move to menu 1-1
2 Cooling Zone 1
Move to menu 1-2
3 Defrost Zone 1
Move to menu 1-3
4 Evap. fan
Move to menu 1-4
5 Alarm
Move to menu 1-5
6 Frame Heater
Move to menu 1-6
7 Cooling Zone 2
Move to menu 1-7
Only shown when two-zone operation is set (Menu 6-1)
8 Defrost Zone 2
Move to menu 1-8
Only shown when two-zone operation is set (Menu 6-1)
Menu 1-1 Temp. Sensor
TEMPERATUR Pos: XXXXX
Temp. R2.1 xxx °C
Current supply air temperature Input Z11/ Z12
Temp. R4.1 xxx °C
Current return air temperature Input Z21/ Z22
Temp. R1.1 xxx °C
Current evaporator defrost termination temperature Input Z31/ Z32
Temp. R4.2 xxx °C
Current return air temperature Input Z41/ Z42
Temp. R1.2 xxx °C
Current evaporator defrost termination temperature Input Z51/ Z52
Temp. R2.3 xxx °C
Current supply air temperature Input Z61/ Z62
Temp. R4.3 xxx °C
Current return air temperature Input Z71/ Z72
Temp. R1.3 xxx °C
Current evaporator defrost termination temperature Input Z81/ Z82
Temp. R4.4 xxx °C
Current return air temperature Input Z91/ Z92
Temp. R1.4 xxx °C
Current evaporator defrost termination temperature Input Z01/ Z02
Содержание UA 400
Страница 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1 ...
Страница 133: ...Firmware V3 15 21 04 2021 133 401 Upper case and lower case can be toggled by tapping the MODE button ...
Страница 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD ...
Страница 244: ...Firmware V3 15 21 04 2021 244 401 ...
Страница 324: ...Firmware V3 15 21 04 2021 324 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint ...
Страница 357: ...Firmware V3 15 21 04 2021 357 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint ...
Страница 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay ...
Страница 372: ...Firmware V3 15 21 04 2021 372 401 ...