Firmware V3.15
21.04.2021
344/401
•
•
•
•
Menu 6-2 Controller
CONTROLLER POS: XXXXX
1 Type and Version
Move to menu 6-2-1
2 Temp. Display
Move to menu 6-2-2
3 Alarm Delay
Move to menu 6-2-3
4 230V Inputs
Move to menu 6-2-4
5 Sensor Type
Move to menu 6-2-5
Menu 6-2-1 Type and Version
VERSION POS: XXXXX
Entry
Default
Ctrlr. Type XXXXXXX
Controller type set by DIP Switch S3
–
UR141NK
Software Ver.: XXXX
Software version of case/cold-room controller
–
x.yy
Serial No.: XXXXXX
Device No. of case/cold-room controller
–
Master/Sl. Mode XXX
Synchronized defrosting in master-slave mode
(ON/OFF)
–
Menu 6-2-2 Temp. Display
DISPLAY POS: XXXXX
Entry
Default
Offset XX K
Offset for temperature display
-10..10
0K
Alarm symbol X
Show alarm symbol on BT 30 Temperature
Display
,
, (Y/N)
N
Menu 6-2-3 Alarm Delay
ALARMDELAY POS: XXXXX
Entry
Default
Sensor Fault XX m
Sensor break alarm delay
0..30
15 min
High/Low Temp. XX m
High/low temperature alarm delay
0..150
90 min
Door open XX m
Cold-room door open alarm delay
0 .. 60
60 m
No Defrost XX h
No defrost alarm delay
--, 2..168
30 h
Selfholding X
NO: Automatic reset of non- transient alarms.
YES: Alarms must be reset manually.
,
, (Y/N)
N
Содержание UA 400
Страница 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1 ...
Страница 133: ...Firmware V3 15 21 04 2021 133 401 Upper case and lower case can be toggled by tapping the MODE button ...
Страница 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD ...
Страница 244: ...Firmware V3 15 21 04 2021 244 401 ...
Страница 324: ...Firmware V3 15 21 04 2021 324 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint ...
Страница 357: ...Firmware V3 15 21 04 2021 357 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint ...
Страница 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay ...
Страница 372: ...Firmware V3 15 21 04 2021 372 401 ...