ENG
24
3.4. MAIN BOARD
Item
Ref. Description
Comment
1
LOOP CARD
Loop input, output and mesh
connection. They are assembled
from left to right. Up to 4 cards
2
MAIN
PROCESSOR
3
ETHERNET
It connects the control panel to the
network and allows:
Automatic clock update, Connection
to other control panels,
Upload/download of databases and
configurations
Firmware update
4
SD READER
Card reader for factory use only
5
BATTERY
CR2031-type button cell for the internal
clock.
6
USB TYPE A
Allows databases, configurations or
software updates to be uploaded/
downloaded using a PEN DRIVE.
7
BUZZER
It sounds if there is an alarm, fault or event
set as an alarm.
8
USB TYPE B
Port
for
uploading/downloading
databases and configurations of the
control panel, updating the firmware
from a PC that has the configuration
software installed.
9
BATTERY
STARTER
SWITCH
It allows the control panel to be started
without mains power if the battery has
enough charge.
10
BAT
Power supply input connector of the control
panel via the auxiliary battery. Only use the
recommended batteries (see section 3.11).
11
SW2
Establish the identification of the
cabinet in the combined tower control
panel.
12
BAT FUSE
10 A battery fuse
13
SW3
Item
Ref. Description
Comment
14
EN
UNE
ISO
J32
Jumper for Buzzer off. Disconnects the
internal buzzer ONLY in case of a SYSTEM
FAULT.
15
J7
Jumper for Earth Leakage Detection.
Disconnects the fault generated by an
earth leakage.
16
RS485
External channel input reserved for
future applications
17
RS485
External channel output reserved for
future applications
18
AUX FUSE
Auxiliary output protection fuse.
19
SND1 FUSE
Sounders output 1 protection fuse. 500 mA
20
24 VDC AUX.
24 V 500 mA auxiliary output connector
21
SND1
Monitored output 1 connector for sounders
22
SND2 FUSE
Sounders output 2 protection fuse. 500 mA
23
SND2
Monitored output 2 connector for sounders
24
R.ALARM
Output contacts for alarm relay
type C-NO-NC, voltage-free.
25
R.FAULT
Output contacts for fault relay type
C-NO-NC, voltage-free.
26
VIN
24 Vdc power supply input for the main base
card.
27
GENERAL FUSE
General protection fuse for the base control
card
28
EXPANSION
Connector for additional expansion card
29
EXPANSION
INPUT
CONNECTOR
Input connector for the configuration of
various control panel sections
30
EXPANSION
OUTPUT
CONNECTOR
Output connector for the configuration of
various control panel sections
Содержание CAD-250
Страница 1: ...ENG INSTALLATION GUIDE ENG ...
Страница 2: ...ENG 2 ...
Страница 3: ...3 ENG ...
Страница 17: ...17 ENG 1 3 6 3 2 4 5 ...
Страница 21: ...21 ENG 1 2 3 5 4 6 7 ...
Страница 81: ...81 ENG ...
Страница 82: ...ENG 82 ...
Страница 83: ...83 ENG ...
Страница 84: ...ENG 84 MI 375 en 2020 c CAD 250_MI_372_en_2019 d ...