2. ASSEMBLY GUIDE
This section will explain how to attach the control panel securely in its
final location. Before fixing the control panel to the wall, read this section
carefully and plan how you will install it in order to prevent future faults
or unnecessary actions.
2.1. CABLE ENTRIES
The CAD-250 has various cable entries. The entry covers can be
removed easily using pliers.
Do not remove more covers than those you will use to prevent
any openings on the box. Close them before connecting the
power supply to the control panel. Otherwise, you will leave
zones exposed that have voltage risks.
To remove a cover, bend it with pliers several times until it comes off.
1 ENTRIES FOR CABLE GLANDS
The upper part of the box has 28 pre-cut entries with a diameter of
24 mm in order to use cable glands. These holes are useful when
the cables come through tubes or in a hose.
2 REAR CABLE ENTRY
The back of the box has a large rectangular shape in the upper area.
Use this entry when the cables to enter come directly out of the wall
on which you are going to install the control panel.
3 SIDE CABLE ENTRY
The control panel has two rectangular cuts in the lower area on the
right and left sides. These entries are practical if you are using a
conduit to guide the cables.
4 CABLE ENTRY FOR ASSEMBLING VARIOUS SECTIONS
The upper and lower faces have two small rectangular cuts on the
left side that allow the passage of the expansion cables in case of a
tower-type device (up to a
maximum of 4 cabinets
can be installed,
see section 1.9.).
5 ADDITIONAL REAR INPUT
The back has a rectangular shape in the lower area, which may be
useful, for example, if you install the control panel in a cabinet.
6 LOWER INPUT
The lower face has a rectangular shape, which is useful, for example,
for connecting an external power supply with the UNE EN54-4
certification.
7 CABLE ENTRY FOR THE MAIN POWER SUPPLY
Do not cross the main power supply cable over the control card.
To do this, use the cable entry on the right to insert the cable to
connect to the mains network, as it is closest to the control panel's
AC connector.
L1 out
L3
and 4
L1 in
L2 out
L2 in
L5 and 6
L7 and 8
RAlarm
RFault SND1
SND2
24V Aux
RS485
RJ45
RJ45
230 Vac
230 Vac
Содержание CAD-250
Страница 1: ...ENG INSTALLATION GUIDE ENG ...
Страница 2: ...ENG 2 ...
Страница 3: ...3 ENG ...
Страница 17: ...17 ENG 1 3 6 3 2 4 5 ...
Страница 21: ...21 ENG 1 2 3 5 4 6 7 ...
Страница 81: ...81 ENG ...
Страница 82: ...ENG 82 ...
Страница 83: ...83 ENG ...
Страница 84: ...ENG 84 MI 375 en 2020 c CAD 250_MI_372_en_2019 d ...