67
ENG
MAXIMUM LOAD:
28V 10A contacts
24 Vdc AUXILIARY OUTPUT VALUES
OUTPUT VOLTAGE:
From 26 Vdc to 28 Vdc
LOOP OUTPUTS
OUTPUT VOLTAGE:
26 Vdc to 33 Vdc (Detnov protocol)
MAXIMUM LOAD:
0.45 A
MAXIMUM
DEVICES/LOOP:
Up to 250 devices (*)
(*) The number of elements may be
limited by local requirements, system
autonomy and the requirements of the
emergency plan.
Take into account the consumption of
the devices at the most unfavourable
time, for e.g. alarm or evacuation in
relation to the maximum current of the
loop and the necessary autonomy.
The specifications and features
described in this manual may be subject
to modification without prior notice by
the manufacturer.
MECHANICAL SPECIFICATIONS
MATERIALS:
Iron sheet housing with a thickness
of 1.2 mm. ABS front with V0 fire
resistance
DIMENSIONS:
Maximum measurements of the
control panel (in mm):
Width: 533 / Height: 450 /
Depth: 225
WEIGHT :
Without batteries: 12.5 kg
With NP24-12 batteries: 30.5 kg
ENVIRONMENTAL SPECIFICATIONS
CLIMATE
CLASSIFICATION:
3K5, (IEC 721-2-3)
OPERATING
TEMPERATURE:
from -5°C to +40°C
HUMIDITY:
from 5% to 95% RH
PANEL
PROTECTION:
IP 30, (EN 60529)
EMC
(electromagnetic
compat.):
Immunity EN 50130-4
I
NDICATION SCREEN
1
0” TOUCHSCREEN:
IPS, 1024x600 pixel resolution,
300 dpi touch resolution
PRIMARY
INDICATORS:
Service, Alarm, Disabled, Fault,
Test, Out of service, Power supply
fault, System fault, Earth leakage,
Sounder delay, Sounder fault/
disablement, Disabled relays.
ZONE INDICATORS
(Optional):
250 alarm indications and 250 fault
indications
CONTROL KEYS
PRIMARY
CONTROLS:
Switch On Sounders, Silence
Sounders, Silence Buzzer, Reset.
EXTERNAL
CONNECTIONS:
2 USB ports, 1 Ethernet port
1 RS232 port for printer
CABLE ENTRIES:
10 entries with a diameter of more
than 23 mm
421 x 55 mm on the back
EXPANSION
INPUTS:
2 (upper and lower)
measuring 50 mm x 15 mm
CONDUIT ENTRIES:
2 side entries (left and right)
measuring 100 mm x 35 mm
EXTERNAL POWER
INPUTS:
Rear input measuring 50 x 74 mm
Lower input measuring 35 x 75 mm
ELECTRICAL SPECIFICATIONS
CLASSIFICATION:
Class I facility (the panel must be
earthed)
POWER SUPPLY:
88 V-264 V~(ac),
3 A (115 V), 2 A (230 V)
FUSE:
4 A
INTERNAL
BATTERIES:
24 Ah-12 V
OUTPUTS:
2 Sounder outputs / 2 Fault outputs
/ 1 Auxiliary output of 24 V / 8 Loop
outputs (optional)
SOUNDER OUTPUT VALUES
TYPE:
Inverted voltage.
OUTPUT VOLTAGE:
active 26 to 28 V /
inactive -6 V to -7 V
MAXIMUM LOAD:
0.45 A
FUSE:
0.5 A
MONITORING:
Open circuit and short circuit
RELAY OUTPUT VALUES
TYPE:
Single pole changeover switch
Содержание CAD-250
Страница 1: ...ENG INSTALLATION GUIDE ENG ...
Страница 2: ...ENG 2 ...
Страница 3: ...3 ENG ...
Страница 17: ...17 ENG 1 3 6 3 2 4 5 ...
Страница 21: ...21 ENG 1 2 3 5 4 6 7 ...
Страница 81: ...81 ENG ...
Страница 82: ...ENG 82 ...
Страница 83: ...83 ENG ...
Страница 84: ...ENG 84 MI 375 en 2020 c CAD 250_MI_372_en_2019 d ...