43
ENG
No. Condition
Colour/
status
Description
8
POWER SUPPLY
FAULT
Amber
Permanent
Critical system fault. In this case, the system is not
operative.
9
EARTH LEAKAGE
FAULT
Amber
Intermittent
Some of the system lines are earthed directly or
indirectly.
10
RESERVED 1
Amber
Programmable indicator for customisable function
11
TIMED
SOUNDERS
Amber
Programmable indicator for customisable function
12
FAULT/
CANCELLED
SOUNDERS
Amber
Permanent
Programmable indicator for customisable function
13
OUTPUTS
CANCELLED
Amber
Intermittent
Indicates that there is a fault in the sounder circuit
or in a loop sounder
14
RESERVED 2
Amber
Permanent
Indicates that there is a control element or relay
disabled on the main board.
15
RESERVED 3
Amber
Programmable indicator for customisable function.
4.3. PRIMARY CONTROLS
No.
Function
Symbol
Description
16
ACTIVATE SOUNDERS
Press the button to activate the sounders.
EVACUATION
17
SILENCE SOUNDERS
Press the button to silence the sounders. The
sounders will be reactivated if a new alarm
event arrives.
18
RELAYS DISABLED
Press the button to silence the acoustic signal
of the control panel.
The signal reactivates when a new event is
received.
19
RESET
Press to reset the system. All alarm and fault
conditions, as well as all control activations
will be reset. If the incidents persist, the
activation and operating process will be
reactivated again.
4.4. INITIAL START-UP
If you followed the initial steps of this guide, a GREEN LIGHT will light
up on the left part of the door (MAIN PANEL) and the screen will show:
a. A status bar that indicates that the control panel is starting up, please
wait.
b. The STANDBY SCREEN will appear, which shows the basic control
panel information.
Содержание CAD-250
Страница 1: ...ENG INSTALLATION GUIDE ENG ...