6.3. CLEANING
The control panel must be cleaned regularly with a soft cloth dampened
with water. Do not use solvents
Press on the
MODE
drop-down menu and select
TEST
Note that in the device TREE, the
MODE
field of the device (1.1) has
changed to "
T".
While the test mode is enabled in an area or zone, the alarm signals
sent by the devices contained in that area or zone will be saved in the
event log of the control panel as events sent in
TEST
mode and no
manoeuvre will be initiated. The input device will turn on the indicator
light for a few seconds and after a while the device will reset.
To change an area to test mode, the procedure is similar. Access the
AREAS
submenu, in the
SECTORISATION
category, and select the one
you wish to modify. Via the
CONFIGURATION TABLE
, change its mode.
⚠
WARNING!:
Remember that once you have completed the
maintenance tasks of the detection network, you must return the zone or
area to ENABLED mode.