Initialisation
[3] is selected if you wish to use
the unit
’
s factory setting.
Procedure for initialisation:
1. Select
Initialisation
[3].
2. Disconnect the mains voltage and wait until the
light in the display has disappeared.
3. Connect the mains voltage.
4. An initialisation is performed in all parameters
in all Setups, with the exception of parameters
500
Address
, 501
Baudrate
, 600-605
Operating
data
and 615-617
Fault log
.
✭
= factory setting. () = display text [] = value for use in communication via serial communication port