VLT
®
FCD Series
■
Control Word according to FC protocol
To select
FC protocol
in the control word, parameter
512
Telegram Profile
must be set to
FC protocol
[1].
The control word is used to send commands from a
master (e.g. a PC) to a slave (frequency converter).
Bit
Bit = 0
Bit =1
00
Preset ref. lsb
01
Preset ref. msb
02
DC braking
03
Coasting stop
04
Quick stop
05
Freeze outp. freq.
06
Ramp stop
Start
07
Reset
08
Jog
09
Ramp 1
Ramp 2
10
Data not valid
Data valid
11
No function
Relay output
12
No function
Digital output
13
Select Setup, lsb
14
Select Setup, msb
15
Reversing
Bit 00/01:
Bit 00/01 is used to select between the two
pre-programmed references (parameters 215-218
Preset reference
) according to the following table:
Preset ref.
Parameter
Bit 01
Bit 00
1
215
0
0
2
216
0
1
3
217
1
0
4
218
1
1
NB!:
In parameter 508
Selection of preset
reference
a selection is made to define how
Bit 00/01 gates with the corresponding
function on the digital inputs.
Bit 02, DC brake:
Bit 02 =
’
0
’
causes DC braking and stop. Brake
voltage and duration are preset in parameters
132
DC brake voltage
and parameter 126
DC
braking time
. Note: In parameter 504
DC brake
a
selection is made to define how Bit 02 gates with
the corresponding function on a digital input.
Bit 03, Coasting stop:
Bit 03 =
’
0
’
causes the frequency converter to
immediately "let go" of the motor (the output transistors
are "shut off"), so that it coasts to a standstill.
Bit 03 =
’
1
’
causes the frequency converter to be able
start the motor if the other starting conditions have
been fulfilled. Note: In parameter 502
Coasting stop
a selection is made to define how Bit 03 gates with
the corresponding function on a digital input.
Bit 04, Quick stop:
Bit 04 =
’
0
’
causes a stop, in which the motor
’
s
speed is ramped down to stop via parameter
212
Quick stop ramp-down time
.
Bit 05, Freeze output frequency:
Bit 05 =
’
0
’
causes the present output frequency
(in Hz) to freeze. The frozen output frequency can
now only be changed by means of the digital inputs
programmed to
Speed up
and
Speed down
.
NB!:
If
Freeze output
is active, the frequency
converter cannot be stopped via Bit 06
Start
or via a digital input. The frequency converter
can only be stopped by the following:
•
Bit 03 Coasting stop
•
Bit 02 DC braking
•
Digital input programmed to
DC braking
,
Coasting
stop
or
Reset and coasting stop
.
Bit 06, Ramp stop/start:
Bit 06 =
’
0
’
causes a stop, in which the motor
’
s
speed is ramped down to stop via the selected
ramp down
parameter.
Bit 06 =
’
1
’
causes the frequency converter to be able
to start the motor, if the other starting conditions have
been fulfilled. Note: In parameter 505
Start
a selection
is made to define how Bit 06 Ramp stop/start gates
with the corresponding function on a digital input.
Bit 07, Reset:
Bit 07 =
’
0
’
does not cause a reset.
Bit 07 =
’
1
’
causes the reset of a trip. Reset is
activated on the signal
’
s leading edge, i.e. when
changing from logic
’
0
’
to logic
’
1
’
.
Bit 08, Jog:
Bit 08 =
’
1
’
causes the output frequency to be
determined by parameter 213
Jog frequency
.
MG.04.B7.02 - VLT is a registered Danfoss trademark
82