VLT
®
FCD Series
Programming, FCD
300
Bit 09, Selection of ramp 1/2:
Bit 09 = "0" means that ramp 1 is active (parameters
207/208). Bit 09 = "1" means that ramp 2
(parameters 209/210) is active.
Bit 10, Data not valid/Data valid:
Is used to tell the frequency converter whether the
control word is to be used or ignored. Bit 10 =
’
0
’
causes the control word to be ignored, Bit 10
=
’
1
’
causes the control word to be used. This
function is relevant, because the control word is
always contained in the telegram, regardless of which
type of telegram is used, i.e. it is possible to turn
off the control word if you do not wish to use it in
connection with updating or reading parameters.
Bit 11, No function:
Bit 11 = relay output control.
Bit 12, No function:
Bit 12 = digital output control.
Bit 13/14, Selection of Setup:
Bits 13 and 14 are used to choose from the four
menu Setups according to the following table:
Setup
Bit 14
Bit 13
1
0
0
2
0
1
3
1
0
4
1
1
The function is only possible when
Multi-Setups
is
selected in parameter 004
Active Setup
.
Note: I parameter 507
Selection of Setup
a selection
is made to define how Bit 13/14 gates with the
corresponding function on the digital inputs.
Bit 15 Reversing:
Bit 15 =
’
0
’
causes no reversing.
Bit 15 =
’
1
’
causes reversing.
Note: In the factory setting reversing is set to
digital
in parameter 506
Reversing
. Bit 15 only
causes reversing when either
Ser. communication
,
Logic or
or
Logic and
is selected.
■
Status Word according to FC Profile
The status word is used to inform the master
(e.g. a PC) of the slave
’
s (frequency converter)
mode.
Slave
⇒
Master.
Bit
Bit = 0
Bit =1
00
Control ready
01
Drive ready
02
Coasting stop
03
No trip
Trip
04
Not used
05
Not used
06
Trip lock
07
No warning
Warning
08
Speed
≠
ref.
Speed = ref.
09
Local control
Ser. communi.
10
Outside
frequency range
Frequency limit
OK
11
Motor running
12
13
Voltage warn.
14
Current limit
15
Thermal warn.
Bit 00, Control ready:
Bit 00 =
’
1
’
.
The frequency converter is
ready for operation.
Bit 00 =
’
0
’
.
The frequency converter is
not ready for operation.
Bit 01, Drive ready:
Bit 01 =
’
1
’
. The frequency converter is ready for
operation, but there is an active coasting command
via the digital inputs or via serial communication.
Bit 02, Coasting stop:
Bit 02 =
’
0
’
. The frequency converter has
released the motor.
Bit 02 =
’
1
’
. The frequency converter can start the
motor when a start command is given.
Bit 03, No trip/trip:
Bit 03 =
’
0
’
means that the frequency converter
is not in fault mode.
Bit 03 =
’
1
’
means that the frequency converter
is tripped, and that it needs a reset signal for
operation to be reestablished.
MG.04.B7.02 - VLT is a registered Danfoss trademark
83