VLT
®
FCD Series
025 Quick Menu setup
(QUICK MENU SETUP)
Value:
[Index 1 - 20] Value: 0 - 999
✭
000
Function:
In this parameter you define which parameters are
required in the Quick Menu when parameter 024
User-defined Quick Menu
is set to
Active
[1]
´
.
Up to 20 parameters can be selected for the
user-defined Quick Menu.
NB!:
Please note that this parameter can only be set
using an LCP 2 control panel. See
Order form
.
Description of choice:
The Quick Menu is set up as follows:
1. Select parameter 025
Quick Menu setup
and press [CHANGE DATA].
2. Index 1 indicates the first parameter in Quick
Menu. You can scroll between the index numbers
using the [+ / -] keys. Select Index 1.
3. Using [< >] you can scroll between the
three figures. Press the [<] key once ad
the last number in the parameter number
can be selected using the [+ / -] keys.
Set Index 1 to 100 for parameter 100
Configuration
.
4. Press [OK] when Index 1 has been set to 100.
5. Repeat steps 2 - 4 until all parameters required
have been set to the Quick Menu key.
6. Press [OK] to complete the Quick Menu setup.
If parameter 100
Configuration
is selected at
Index 1, Quick Menu will start with this parameter
every time Quick Menu is activated.
Please note that parameter 024
User-defined Quick
Menu
and parameter 025
Quick Menu setup
are
reset to the factory setting during initialisation.
026
LED Status
(LED STATUS)
Value:
✭
Overload (OVERLOAD)
[0]
Therm. warn/alarm 36 (OVERTEMP)
[1]
Thermistor/ETR (THERMAL MOTOR)
[2]
Digital input 18 (DIGITAL INPUT 18)
[3]
Digital input 19 (DIGITAL INPUT 19)
[4]
Digital input 27 (DIGITAL INPUT 27)
[5]
Digital input 29 (DIGITAL INPUT 29)
[6]
Digital input 33 (DIGITAL INPUT 33)
[7]
As relay par. 323 (AS RELAY / P323)
[8]
As dig.outp. par. 341 (AD DIG. OUT. / P341)
[9]
As mech.brake output
(AS MECH. BRAKE OUTPUT)
[10]
Function:
This parameter enables the user to visualize different
situations using the Status LED.
Description of choice:
Select the function to be visualized.
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.04.B7.02 - VLT is a registered Danfoss trademark
38