VLT
®
FCD Series
Programming, FCD
300
NB!:
If
Freeze output
is active the frequency converter
can only be stopped if you select
Motor coast
,
Quick stop
or
DC braking
via a digital input.
Speed up
and
Speed down
are selected if digital
control of the up/down speed is required. This
function is only active if
Freeze reference
or
Freeze
output frequency
has been selected.
If
Speed up
is active the reference or output frequency
will be increased, and if
Speed down
is active the
reference or output frequency will be reduced. The
output frequency is changed via the preset ramp
times in parameters 209-210
Ramp 2
.
One pulse (logic
’
1
’
minimum high for 14 ms
and a minimum break time of 14 ms) will lead
to a speed change of 0.1 % (reference) or 0.1
Hz (output frequency). Example:
Term.
29
Term.
33
Freeze ref/
freeze outp.
Function
0
0
1
No speed change
0
1
1
Speed up
1
0
1
Speed down
1
1
1
Speed down
Freeze reference
can be changed even if the frequency
converter has stopped. The reference will also be
saved if the mains are disconnected
Catch-up/Slow-down
is selected if the reference
value is to be increased or reduced by a
programmable percentage value set in parameter
219
Catch-up/Slow-down reference
.
Slow-down
Catch-up
Function
0
0
Unchanged speed
0
1
Increase by % value
1
0
Reduce by % value
1
1
Reduce by % value
Ramp 2
is selected if a shift between ramp 1
(parameters 207-208) and ramp 2 (parameters
209-210) is required. Logic
’
0
’
leads to ramp
1 and logic
’
1
’
leads to ramp 2.
Preset reference, lsb
and
Preset reference, msb
makes it possible to select one of the four preset
references, see the table below:
Preset ref.
msb
Preset ref.
lsb
Function
0
0
Preset ref. 1
0
1
Preset ref. 2
1
0
Preset ref. 3
1
1
Preset ref. 4
Preset reference on
is used for shifting between
remote-controlled reference and preset reference.
It is assumed that External/preset [2] has been
selected in parameter 214
Reference function
. Logic
’
0
’
= remote-controlled references are active, logic
’
1
’
= one of the four preset references is active,
as can be seen from the table above.
Precise stop, inverse
is selected to obtain a high
degree of accuracy when a stop command is
repeated. A logic 0 means that the motor speed is
ramped down to stop via the selected ramp.
Precise start/stop
is selected to obtain a high degree of
accuracy when a start and stop command is repeated.
Pulse reference
is selected if the reference
signal applied is a pulse train (frequency). 0 Hz
corresponds to parameter 204
Minimum reference,
Ref
MIN
. The frequency set in parameter 327/328
Pulse Max 33/29
corresponds to parameter
205
Maximum reference Ref
MAX
.
Pulse feedback
is selected if the feedback signal
used is a pulse train (frequency). In parameter
327/328
Pulse Max 33/29
the maximum pulse
feedback frequency is set.
Pulse input
is selected if a specific number of pulses
must lead to a
Precise stop
, see parameter 343
Precise stop
and parameter 344
Counter value
.
Selection of Setup, lsb
and
Selection of Setup,
msb
gives the possibility to select one of the
four setups. It is, however, a condition that
parameter 004 is set to
Multisetup
.
Reset and start
can be used as a start function.
If 24 V are connected to the digital input, this will
cause the frequency converter to reset and the motor
will ramp up to the preset reference.
Encoder reference
is selected if the reference
signal applied is a pulse train (frequency). 0 Hz
corresponds to parameter 204
Minimum reference,
Ref
MIN
. The frequency set in parameter 327/328
Pulse Max 33/29
corresponds to parameter
205
Maximum reference Ref
MAX
.
Encoder feedback
is selected if the feedback signal
used is a pulse train (frequency). In parameter
327/328
Pulse Max 33/29
the maximum pulse
feedback frequency is set.
Encoder input
is selected if a specific number of
pulses must lead to a
Precise stop
, see parameter 343
Precise stop
and parameter 344
Counter value
.
✭
= factory setting. () = display text [] = value for use in communication via serial communication port