VLT
®
FCD Series
Programming, FCD
300
617 Fault log: Value
(F.LOG: VALUE)
Value:
[Index 1 - 10] Value: 0 - 9999
Function:
In this parameter it is possible to see at which value a
trip occurred. The unit of the value depends on which
alarm is active in parameter 615
Fault log: Fault code
.
Description of choice:
Read out as one value.
618 Reset of kWh counter
(RESET KWH COUNT)
Value:
✭
No reset (DO NOT RESET)
[0]
Reset (RESET COUNTER)
[1]
Function:
Resetting parameter 602
kWh counter
to zero.
Description of choice:
If
Reset
[1]is selected and you press the [OK] key, the
frequency converter
’
s kWh counter is reset to zero. This
parameter cannot be selected via serial communication.
NB!:
When the [OK] key is activated, the
counter is reset to zero.
619 RESET RUNNING HOURS COUNTER
(RESET RUN. HOUR)
Value:
✭
No reset (DO NOT RESET)
[0]
Reset (RESET COUNTER)
[1]
Function:
Resetting of parameter 601
Hours run
to zero.
Description of choice:
If
Reset
[1] is selected and you press the [OK]
key, the frequency converter
’
s parameter 601 is
reset to zero
Hours run
. This parameter cannot
be selected via serial communication.
NB!:
When the [OK] key is activated the
parameter is reset to zero.
620 Operation Mode
(OPERATION MODE)
Value:
✭
Normal operation (NORMAL OPERATION)
[0]
Control card test (CONTROL CARD TEST)
[2]
Initialise (INITIALIZE)
[3]
Function:
In addition to its normal function, this parameter
can be used to test the control card.
There is also the opportunity to perform an
initialisation at the factory setting for all parameters
in all Setups, with the exception of parameters
500
Address
, 501
Baudrate
, 600-605
Operating
data
and 615-617
Fault log
.
Description of choice:
Normal function [0] is used for normal
operation of the motor.
Control card test [2] is selected if you wish to check
the control card
’
s analog/digital inputs, analog/digital
outputs, relay outputs and 10 V and 24 V voltages.
The test is performed as follows:
18 - 19 - 27 - 29 - 33 - 46 are connected.
20 - 55 are connected.
42 - 60 are connected.
01 - 50 are connected.
02 - 53 are connected.
03 - 31B are connected.
Use the following procedure for the control card test:
1. Select control card test.
2. Disconnect the mains voltage and wait until the
light in the display has disappeared.
3. Mount according to drawing and description.
4. Connect the mains voltage.
5. The frequency converter automatically undertakes
a test of the control card.
If the LEDs are flashing a code (4 LEDs alternatively),
the control card test has failed (see the section
Internal faults
for further details. Change the control
card to start up the frequency converter.
If the frequency converter comes into Normal/Display
mode, the test is OK. Remove the test connector
and the frequency converter is ready for operation.
Parameter 620
Operating mode
is automatically
set to
Normal operation
[0].
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.04.B7.02 - VLT is a registered Danfoss trademark
97