VLT
®
FCD Series
All about FCD
300
■
Service
■
Diagnostics
The actual status can be read on the outside of the
FCD products. Five LEDs signal the actual status of
the unit with the meaning described in the table.
Further detailed status information can be obtained
using a local control panel (LCP2 – see photo). This
can be connected on the outside (without opening the
enclosure) if the LCP2-plug shown on the drawing is
installed. The LCP2 is an easy-to -navigate user-friendly
interface used to access and adjust all parameters. It
displays parameters in six different languages.
The FCD 300 holds a log with valuable information
on failure. Information on the most recent 10
faults is stored and indexed in three different
parameters to help diagnosis.
LCP2-plug
Parameter 616
stores the time of the fault as
measured by the internal clock.
Paramet er 617
holds a fault code telling
the type of fault detected.
Parameter 618
stores a measurement relevant for
the case. Typically the intermediate circuit voltage or
output current measured immediately before failure.
Local Control Panel
LED diagnostics on decentralised FCD 300
No
Name
Colour
OK
status
Alternatives
Function
Off
Status of the FCD is OK
1
Status
Yellow
Off
On
Corresponding to parameter setting. For further information see
Design
Guide
- parameter number 26 and DeviceNet manual for specific
DeviceNet signalling
On
OK status for the fild bus used
(Not relevant for non field bus device)
Slow flashing
Local operation or local stop
Fast flashing
Interface working, but no communication with master
(See field bus manual for specific info)
(Not relevant for non field bus device)
2
Bus
Green
On (If bus
option is
present,
else Off)
Off
Status for the field bus
not
OK
(not relevant for non field bus device)
Off
No alarm is present
3
Alarm
Red
Off
Flashing
Flashing while trip/trip lock is present
Off
No warning is present
4
Warning
Yellow
Off
Flashing
Flashing while warning situation is present
On
The unit is supplied by mains power or 24 V DC
5
On
Green
On
Off
Mains power or 24 V DC is missing
MG.04.B7.02 - VLT is a registered Danfoss trademark