INSTRUCTION MANUAL

25B9

SAVE THIS INSTRUCTIONS

LVU-2/5 

THIS PRODUCT CONTAINS A RECHARGEABLE NICKEL-CADMIUM BATTERY.
THE BATTERY MUST BE RECYCLED OR DISPOSED OF PROPERLY.

WWW.MYERSEPS.COM

Ni-cd

UNIVERSAL MICRO INVERTER
PURE SINUSOIDAL AC OUTPUT
OUTPUT VOLTAGE AUTO SETTING EQUAL TO INPUT VOLTAGE
AUTO DIMMING (1-10V) OF CONNECTED LOAD 

IMPORTANT SAFEGUARDS

WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY PRECAUTIONS SHOULD ALWAYS BE FOLLOWED, INCLUDING THE FOLLOWING

READ AND FOLLOW ALL SAFETY INSTRUCTIONS

  1.  To prevent electric shock, switch off the mains power until installation is 
       complete and AC Input power is supplied to this product.

  2.  This product requires an unswitched AC power supply of 120-277V, 50/60Hz.

  3.  Make sure all connections are in accordance with the National or Canadian Electrical 
       code and any local regulations.

  4.  To reduce the risk of electrical shock, disconnect both normal power, emergency power,
       unit and connector of this product before servicing. 

  5.  For emergency operation of LED, incandescent, fluorescent, and screw-base 
       lamps.

  6.  Use this product in 0°C minimum, 50°C maximum ambient temperatures (Ta). To ensure
       the emergency operating time over 90 minutes, the output emergency power of LVU-2/5
       should be maximum of 25W for the LVU-2 and 50W for the LVU-5.

  7.  Use with grounded, UL Listed, damp location rated fixtures. Do not use outdoors. Do 
       not mount it near gas, heaters, air outlets or other hazardous locations.

  8.  Do not attempt to service the batteries. A sealed, non-maintenance battery is used that
       is not field replaceable. Contact the manufacturer for information or service. 

  9.  The use of accessory equipment not recommended by the manufacturer may cause an 
       unsafe condition and void warranty. 

10.  Do not use this product for other than intended use.

11.  Installation and service should be performed by qualified service personnel.

12.  This product should be mounted in locations and at heights where it will not readily be 
       subjected to tampering by unauthorized personnel.

Содержание LVU-2

Страница 1: ...al power emergency power unit and connector of this product before servicing 5 For emergency operation of LED incandescent fluorescent and screw base lamps 6 Use this product in 0 C minimum 50 C maximum ambient temperatures Ta To ensure the emergency operating time over 90 minutes the output emergency power of LVU 2 5 should be maximum of 25W for the LVU 2 and 50W for the LVU 5 7 Use with grounded ...

Страница 2: ...TS Select a convenient location for the LTS so that it can be seen after installation Drill a 1 2 12 mm hole for mounting the LTS Connect the wires from LTS to the LVU 2 5 model according to the wiring diagram on page 3 INSIDE THE LUMINAIRE LVU 2 5 LED test switch CAUTION MAKE CERTAIN THE AC POWER IS OFF AND THE LVU 2 5 UNIT CONNECTOR IS DISCONNECTED UNTIL THE INSTALLATION IS COMPLETE LVU 2 LVU 5 ...

Страница 3: ...ORESCENT INCANDESCENT LUMINAIRE DIM IN BLUE WHITE DIM IN BLUE RED 0 10V DIMMER GRAY OUT NEUTRAL VIOLET VIOLET UNIT CONNECTOR WIRING DIAGRAM FOR 1 10V DIMMABLE EMERGENCY LIGHTING SYSTEM LVU 2 5 TOTAL DIMMABLE POWER LVU 2 UP TO 175W WHITE RED BLACK YELLOW GREEN WHITE BLACK ANY QUANTITY DIM OUT BLUE DIM OUT BROWN ORANGE OUT HOT NEUTRAL GROUND SWITCH HOT LED Test Switch 120 277 VAC 120 277 VAC LED FLU...

Страница 4: ...ed on 3 Monthly Auto Test Monthly Auto Test should be executed every 30 days and to test If the switchover of normal and emergency mode is normal If the emergency function and battery s charging and discharging condition is normal Auto Test time is about 30 seconds 4 Annual Auto Test Annual Auto Test will be executed every 52 weeks after 24 hours full charging and to test If the battery s voltage ...