SiUS341802E
Outline of Control (Indoor Unit)
Functions and Control
70
9.2.2 With Optional Infrared Presence/Floor Sensor
The relationship between remote controller set temperature and control target temperature is
described below.
•
The temperature difference for cooling
⇔
heating mode switching is 5°C (9°F).
•
When using the floor temperature as the control target, the remote controller set temperature is
equal to the actual control target temperature in heating operation.
•
The above also applies to automatic operation.
When setting the suction air thermistor (Default setting)
When using the remote controller thermistor (Field setting is required)
Examples are given to illustrate a control target temperature that satisfies the remote controller set
temperature.
Regarding control target temperature
When using the infrared presence/floor sensor, the temperature around people will be treated as
the control target temperature for operation.
What is the temperature around people?
The temperature around people refers to the temperature of the living space, obtained from the
temperature around the ceiling and the temperature underfoot. The temperature is calculated using
the detected values of the suction air thermistor and the infrared presence/floor sensor.
It is difficult to use only suction air temperature control for underfoot air conditioning.
35 36˚C
31 32 33 34
27 28
30
23 24 25 26
20 21 22
29
16 17 18 19
14 15
Remote controller set temperature
Control target temperature
Remote controller set temperature
Control target temperature
Cooling
Heating
57.2
60.8
69.8
62.6
71.6
64.4
73.4
66.2
75.2
59
68
78.8 80.6 82.4 84.2
77
87.8
96.8
89.6 91.4 93.2
˚F
86
95
Temperature
Remote controller set temperature
Control target temperature
Remote controller set temperature
Control target temperature
Cooling
Heating
35 36˚C
31 32 33 34
27 28
30
23 24 25 26
20 21 22
29
16 17 18 19
14 15
57.2
60.8
69.8
62.6
71.6
64.4
73.4
66.2
75.2
59
68
78.8 80.6 82.4 84.2
77
87.8
96.8
89.6 91.4 93.2
˚F
86
95
Temperature
Содержание Aurora Series
Страница 316: ...Wiring Diagrams SiUS341802E 303 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXLQ72TATJU 2D112580A ...
Страница 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Страница 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Страница 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Страница 320: ...Wiring Diagrams SiUS341802E 307 Appendix RXLQ72 96 120TAYCU RXYQ72 96 120 144 168TAYCU 2D112579A ...
Страница 330: ...Wiring Diagrams SiUS341802E 317 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269C ...
Страница 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Страница 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...