Outline of Control (Indoor Unit)
Functions and Control
80
Note:
When the indoor unit is FXFQ, FXZQ or FXUQ, if the air outlet is set as dual-directional or tri-
directional, the starting conditions will be changed as follows.
Liquid pipe temperature
≤
1°C (33.8°F) (for total of 15 minutes)
or
Liquid pipe temperature
≤
0°C (32°F) (for 1 minute continuously)
During freeze-up prevention operation, the airflow rate is fixed to LL.
(The cancelling conditions are same as the standard.)
0
ºC
(32˚F)
+
7
ºC
(44.6˚F)
10 min.
1 min.
+
1
ºC
(33.8˚F)
t1
t2
t3
t4
+
7
ºC
(44.6˚F)
10 min.
OR
t
>
15
minutes
Freeze-up prevention control
Forced OFF by thermostat
Freeze-up prevention control
Forced OFF by thermostat
Liquid pipe
temperature
Start
Cancel
Start
Cancel
Normal operation
Normal operation
Содержание Aurora Series
Страница 316: ...Wiring Diagrams SiUS341802E 303 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXLQ72TATJU 2D112580A ...
Страница 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Страница 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Страница 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Страница 320: ...Wiring Diagrams SiUS341802E 307 Appendix RXLQ72 96 120TAYCU RXYQ72 96 120 144 168TAYCU 2D112579A ...
Страница 330: ...Wiring Diagrams SiUS341802E 317 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269C ...
Страница 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Страница 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...