SiUS341802E
Capacity Range
General Information
8
4. Capacity Range
4.1
Combination Ratio
RXLQ-TATJU, RXLQ-TAYDU, RXLQ-TAYCU
Notes:
∗
1. If the operational capacity of indoor units is more than 130%, low airflow operation is
enforced in all the indoor units. Refer to page 129 for detail.
∗
2. When outdoor-air processing units (FXMQ-MF) and standard indoor units are connected,
the total connection capacity of the outdoor-air processing units (FXMQ-MF) must not
exceed 30% of the capacity index of the outdoor units. And the connection ratio must not
exceed 100%.
∗
3. It is permitted to use a maximum connection ratio of 130% in some circumstances – please
contact your local Daikin representative for further details.
RXYQ-TAYCU
Notes:
∗
1. RXYQ72TAYCU: 70%
∗
2. If the operational capacity of indoor units is more than 130%, low airflow operation is
enforced in all the indoor units. Refer to page 129 for detail.
∗
3. When outdoor-air processing units (FXMQ-MF) and standard indoor units are connected,
the total connection capacity of the outdoor-air processing units (FXMQ-MF) must not
exceed 30% of the capacity index of the outdoor units. And the connection ratio must not
exceed 100%.
∗
4. It is permitted to use a maximum connection ratio of 130% in some circumstances – please
contact your local Daikin representative for further details.
Combination ratio =
Total capacity index of the indoor units
Capacity index of the outdoor units
Type
Min.
combination
ratio
Max. combination ratio
Types of connected indoor units
Type of connected air treatment
equipments
When using
only FXDQ-M,
FXSQ07-54TA,
FXMQ-PB,
FXAQ-P
When using at
least one
FXFQ07/09,
FXZQ05TA,
FXSQ05TA
When using
other indoor
unit models
FXMQ-MF
When FXMQ-MF
is only connected
When FXMQ-MF
and indoor units
are connected
Single outdoor units
70%
200%
∗
1
180%
∗
1
200%
∗
1
100%
100%
∗
2
∗
3
Double outdoor units
160%
∗
1
160%
∗
1
Type
Min.
combination
ratio
Max. combination ratio
Types of connected indoor units
Type of connected air treatment
equipments
When using
only FXDQ-M,
FXSQ07-54TA,
FXMQ-PB,
FXAQ-P
When using at
least one
FXFQ07/09,
FXZQ05TA,
FXSQ05TA
When using
other indoor
unit models
FXMQ-MF
When FXMQ-MF
is only connected
When FXMQ-MF
and indoor units
are connected
Single outdoor units
50%
∗
1
200%
∗
2
180%
∗
2
200%
∗
2
100%
100%
∗
3
∗
4
Double outdoor units
160%
∗
2
160%
∗
2
Triple outdoor units
130%
∗
2
130%
Содержание Aurora Series
Страница 316: ...Wiring Diagrams SiUS341802E 303 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXLQ72TATJU 2D112580A ...
Страница 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Страница 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Страница 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Страница 320: ...Wiring Diagrams SiUS341802E 307 Appendix RXLQ72 96 120TAYCU RXYQ72 96 120 144 168TAYCU 2D112579A ...
Страница 330: ...Wiring Diagrams SiUS341802E 317 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269C ...
Страница 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Страница 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...