Field Settings from Remote Controller
SiUS341802E
107
Field Settings and Test Operation
Setting of Airflow Rate
Make the following setting according to the ceiling height. The second code No. is set to
01
at the factory.
FXHQ, FXAQ
FXFQ07-24T, FXFQ09-30P, FXUQ18/24P
FXFQ30-48T, FXFQ36/48P, FXUQ30/36P
Airflow Direction Setting
Set the airflow direction of indoor units as given in the table below. (Set when sealing material kit of air discharge
outlet has been installed.) The second code No. is factory set to
01
.
Swing Pattern Settings
(For units with the infrared presence/floor sensor only)
Set the flap operation in swing mode.
With the factory swing, flaps facing each other are synchronized to operate, and flaps placed side by side are set
to swing in an opposite direction to agitate airflow to reduce temperature irregularity.
Conventional swing operation (all direction synchronized swing) can be set onsite.
Mode No.
First Code No.
Second Code No.
Contents
13 (23)
0
01
Standard
02
Slight increase
03
Normal increase
Mode No.
First Code
No.
Second
Code No.
Contents
Ceiling height
4-way Outlets
3-way Outlets
2-way Outlets
13 (23)
0
01
Standard
Lower than
2.7 m
(8-3/4 ft)
Lower than
3.0 m
(10 ft)
Lower than
3.5 m
(11-1/2 ft)
02
High Ceiling 1
Lower than
3.0 m
(10 ft)
Lower than
3.3 m
(10-3/4 ft)
Lower than
3.8 m
(12-1/2 ft)
03
Higher Ceiling 2
Lower than
3.5 m
(11-1/2 ft)
Lower than
3.5 m
(11-1/2 ft)
—
Mode No.
First Code
No.
Second
Code No.
Contents
Ceiling height
4-way Outlets
3-way Outlets
2-way Outlets
13 (23)
0
01
Standard
Lower than
3.2 m
(10-1/2 ft)
Lower than
3.6 m
(12 ft)
Lower than
4.2 m
(13-3/4 ft)
02
High Ceiling 1
Lower than
3.6 m
(12 ft)
Lower than
4.0 m
(13-1/8 ft)
Lower than
4.2 m
(13-3/4 ft)
03
Higher Ceiling 2
Lower than
4.2 m
(13-3/4 ft)
Lower than
4.2 m
(13-3/4 ft)
—
Mode No.
First Code No.
Second Code No.
Contents
13 (23)
1
01
F: 4-direction airflow
02
T: 3-direction airflow
03
W: 2-direction airflow
Mode No.
First Code No.
Second Code No.
Contents
13 (23)
2
01
All direction synchronized swing
02
—
03
Facing swing
Содержание Aurora Series
Страница 316: ...Wiring Diagrams SiUS341802E 303 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXLQ72TATJU 2D112580A ...
Страница 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Страница 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Страница 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Страница 320: ...Wiring Diagrams SiUS341802E 307 Appendix RXLQ72 96 120TAYCU RXYQ72 96 120 144 168TAYCU 2D112579A ...
Страница 330: ...Wiring Diagrams SiUS341802E 317 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269C ...
Страница 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Страница 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...