Troubleshooting by Error Code
SiUS341802E
263
Service Diagnosis
2.62 Transmission Error between Outdoor Units
Error Code
U7
Applicable
Models
All outdoor unit models
Method of Error
Detection
Microcomputer checks if transmission between outdoor units is normal.
Error Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
Connection error of transmission wirings between outdoor unit and external control adaptor for
outdoor unit
Connection error of transmission wirings between outdoor units
Cool/Heat selection setting error
Cool/Heat unified address setting error (functional unit, external control adaptor for outdoor unit)
Defective outdoor unit PCB
Defective external control adaptor for outdoor unit
Содержание Aurora Series